STORAGE &
DISTRIBUTION SYSTEM for
PW / WFI

Storage & Distribution System is required to store and distribute the PW / WFI within the plant. The system ensures stringent quality parameters of Pharmaceutical / Biotech industry. The distribution system is a closed loop system. Closed loop system ensures integrity of the PW & WFI. The entire Storage & Distribution System parameters are monitored & controlled with the help of instruments & equipments mounted on Distribution Skid.

APPLICATIONS

PW / WFI Storage & Distribution System is required for

• Purified Water / WFI Storage

• Distribution of Purified Water / WFI

• For Sanitization of PW Tank & Distribution Loop

• Controlling Microbial Load in WFI / PW

• Rejecting High Conductivity PW / WFI

• Sterilization Process Management
WFI Tank & Distribution Loop

Features

• PW and WFI Storage Tanks are manufactured as per cGMP guidelines and ASME VIII, DIV 1 standard

• Storage tanks can be plain, jacketed or limpet type. Jacketed and limpet tanks are provided suitable rockwool / glasswool insulation and AISI 304 stainless steel cladding

• If required, provision of electric heating can also be provided with suitable insulation & cladding

Process nozzles will be flushed sanitary flange type

• To make sure optimum cleanability, all tanks are Riboflavin tested

• PW / WFI tanks are provided with necessary accessories for reliable operation

• IPC & PLC based fully automated plant complies with 21 CFR Part 11 & GAMP 5

• Fully drainable sanitary pumps are selected to maintain minimum velocity of 1.2 m/s in the return line at peak load consumption

• Two pumps (Duty / Stand by) are provided to ensure continuous hassle-free operation along with swing arm assembly for changeover

• Distribution skid is provided with instruments to monitor parameters like temperature, conductivity, pressure, flow rate, velocity and also TOC count

• Distribution piping is designed for minimum dead leg criterion of < 1.5 D

• Distribution Loop tubes are semi seamless tubes as per ASTM A270

• All contact parts MOC is AISI 316L Stainless Steel and electro polished to less than 0.4 Rasurface finish and Non-Contact parts are AISI 304 Stainless Steel

• The Distribution loop is designed for 100% drainability by maintaining the minimum slope of 1:100

• All weld joints in the loop are orbital welded using high purity (99.99%) argon gas and can be inspected by boroscopy machine

• Complete set of documentation and certificates to ensure compliance with regulatory authority. We provide DQ, OQ, IQ, FAT & SAT. Also assist client to develop PQ

A system designed to store and circulate Purified Water (PW) or Water for Injection (WFI) throughout pharmaceutical or biotech facilities, ensuring consistent water quality at all user points.

It prevents microbial growth and maintains water quality by eliminating stagnation, typically with loop velocities ≥1 m/s.

Pharmaceuticals, biotechnology, injectables, cosmetics, food & beverage, and personal care sectors, where ultra-pure water is critical to product safety and compliance.